Flash Tanks
For
flashing of high pressure condensate into steam and low pressure
heating supply mains
Reduce steam pressure prior to returning to either condensate tanks,
boilers or discharge into sewer mains
Carbon Steel Construction
Lined Tanks (Cement and Epoxy)
“EPOXOLINE” - This superior tank lining has excellent resistance
to corrosive
hot water.
The polymer structure is odorless, tasteless, non-toxic, and has
excellent
resistance to thermal shock and conforms to US FDA & USDA requirements
for
coatings in contact with food and drinking water.
Service capabilities for potable water up to 180° F. dry and wet
temperature.
“CEMENTLINE” - Another time tested lining for protection against
corrosion in
steel
hot water tanks.
Wendland’s cement lining is specially formulated hydro-plastic cement
for
withstanding corrosive hot water to 212° Fahrenheit.
Lined Tanks (Glass)
For
storage of domestic & non-domestic cold or hot water
Carbon Steel Construction
Baked on glasslining process on interior provides years of reliable
service
Vertical ASME Air Receiver/Chill
Water Storage Tanks
Carbon Steel Construction
Maximum Temperature 650º F
Primed & Painted Exterior
Chilled Water Buffer Tanks
Designed for chilled water systems with insufficient water volume
capacity, in relation to the chiller capacity. Relatively low water
volume systems require additional “buffer” capacity for the system to
eliminate problems such as excessive chiller cycling, poor temperature
control, and erratic system operation. The properly sized American
Wheatley CBT tank adds the necessary volume to “buffer” the system.
Carbon Steel Construction
Exterior Primer Painted
Max Design Temp: 450F
Max Design Press: 125 PSI